Transformer On-Load Tap-Changer Tester

0 Comments /

Transformer On-Load Tap-Changer Tester | Detailed introduction of technical principles

The principle of a transformer load switch tester is to simulate actual switch operation and simultaneously measure its key mechanical and electrical parameters to evaluate switch performance.

The core consists of two parts:

1. Time Characteristic Test: The instrument controls the switch to perform opening/closing operations and records the on/off times of its auxiliary contacts. By measuring the movement time of the moving contact (e.g., opening/closing time, synchronicity, bounce time), the normality and speed of its mechanical operating mechanism are determined.

2. Loop Resistance Test: With the switch closed, the instrument outputs a constant DC current (e.g., 100A) to its conductive circuit using the DC voltage drop method, and simultaneously measures the small voltage drop generated across the switch. The loop resistance is calculated based on Ohm's law. The resistance value sensitively reflects whether the contact is good, whether there is burning, or insufficient pressure.

By comparing the measured data with standard values, the mechanical and electrical condition of the switch can be comprehensively evaluated. Transformer On-Load Tap Changer Tester, Transformer On-Load Tap Changer Analyzer

Digital Transformer On-Load Tap Changer Tester 1A 3-Channel

Transformer load switch tester, used to measure the transition waveform, transition time, instantaneous transition resistance value, and three-phase synchronicity of transformer on-load tap changers.

Main Unit
1. Built-in precision constant current source with complete and reliable protection circuit.

2. Can test with or without windings.

3. Built-in embedded PC-104 industrial computer, high speed, large storage capacity.

4. 6-channel high-speed synchronous data sampling.

Operating Interface
1. 5.7-inch backlit wide-temperature LCD, clear display under sunlight.

2. Graphical and text display results.

3. T9 input method, can input numbers, letters, Chinese characters, and various symbols.

Data Storage

1. 1GB main unit storage capacity: Stores tens of thousands of test data sets.

2. External USB flash drive storage function: Stores even more data.

3. USB flash drive data synchronization function: Convenient data exchange.

4. Can directly open data files on USB flash drives.

5. Tree-structured storage: Stores data by station name, number, and tap position for easy data retrieval.

Online Functionality

6. Equipped with Windows version of "OTS Data Management Software".

7. USB and RS232 online functionality.

8. Comprehensive PC data management and analysis functions.

Transformer Load Cell Switch Tester, Transformer On-Load Switch Tester, Transformer Turns Ratio Test Kit MS-207T, Transformer On-Load Tap Changer Tester, Transformer On-Load Tap Changer Analyzer, Digital Transformer On-Load Tap Changer Tester

Sample Block Quote

Nam tempus turpis at metus scelerisque placerat nulla deumantos sollicitudin delos felis. Pellentesque diam dolor an elementum et lobortis at mollis ut risus. Curabitur semper sagittis mino de condimentum.

Sample Paragraph Text

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Morbi ut blandit risus. Donec mollis nec tellus et rutrum. Orci varius natoque de penatibus et magnis dis parturient montes, nascetur ridiculus mus. Ut consequat quam a purus faucibus scelerisque. Mauris ac dui ante. Pellentesque congue porttitor tempus. Donec sodales dapibus urna sed dictum.

Leave a comment

All blog comments are checked prior to publishing
You have successfully subscribed!