No partial discharge withstand voltage combination test system
The 145kV power system GIS AC withstand voltage test without partial discharge is applicable to test items with a maximum capacitance of <0.0001F/bay (based on 3 bays + 9m GIS internal busbar ≤0.001μF), a total capacitance of ≤0.004uF, a test frequency of 100Hz, and a maximum test voltage of 235kV.
Main Features:
1. High voltage is fully enclosed in a shielded chamber, ensuring safe and reliable testing.
2. Overall partial discharge can be controlled within 5 pc.
3. Compact size minimizes space usage and lightweight components.
4. Built-in high-voltage disconnect switch enables multi-purpose use.
5. Easy connection: Direct connection to the test object makes testing more convenient.
6. Durable structure capable of withstanding long-distance transportation.
7. Reduced system power capacity requirements.
Technical Parameters
1. Output power 50 kW
2. Input voltage 380 V ± 10%, three-phase, 50 Hz
3. Output voltage: Single-phase 0-350 V (sine wave), continuously adjustable.
4. Output waveform: Pure sine wave
5. Output waveform distortion <1.0%
6. Output voltage instability <1.0%
7. Voltage resolution 0.1 V
8. Output current 0-142.8 A
9. Cooling method: Forced air cooling
10. Frequency adjustment range 20-300 Hz
11. Frequency resolution 0.01Hz
12. Frequency instability <0.05%
13. Noise level <85dB
14. Partial discharge <10pC
15. Insulation rating 1.1Uo/1min
16. Continuous operating time >180 minutes at rated power