MSVLF-80kV 1.1uFultra low frequency generator
30kV/40kV/50kV/60kV/80/90kV
This device is particularly suitable for withstand voltage testing of electrical equipment with large equivalent insulation capacitance (e.g., power cables, power capacitors, large and medium-sized generators and motors).
1. Advanced technology: Adopts digital frequency conversion technology and microcomputer control; the entire testing process, including voltage boosting, voltage reduction, measurement, and protection, is fully automated.
2. Easy operation: Simple wiring and convenient use.
3. Comprehensive protection: Multiple protection features (overvoltage protection, high and low voltage side overcurrent protection) with rapid response (action time ≤10ms); the instrument is safe and reliable.
4. Safe and reliable: Low-voltage connection between the controller and high-voltage generator; photoelectric control ensures safe and reliable operation.
5. Adopts a high and low voltage closed-loop negative feedback control circuit, resulting in no capacitive rise effect in the output.
6. Complete configuration: Capacitive touch screen, LCD Chinese character display, automatic storage, and automatic printing.
7. Wide test range: Multiple frequency options of 0.1Hz, 0.05Hz, and 0.02Hz provide a wide test range.
8. Small size and light weight, especially suitable for outdoor work.
9. English and Chinese language switching function.
10. Performance comparison of the ultra-low frequency 0.1Hz test device with other withstand voltage test equipment.
1. Output rated voltage: 30kV/40kV/50kV/60kV/80/90kV/1.1uF
2. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
3. Load capacity: 0.1Hz maximum 1.1µF, 0.05Hz maximum 2.2µF, 0.02Hz maximum 5.5µF
4. Measurement accuracy: 1%
5. Voltage positive and negative peak error: ≤3%
6. Voltage waveform distortion: ≤5%
7. Operating conditions: Indoor and outdoor; Temperature: -10℃-+40℃; Humidity: ≤85%RH
8. Power fuse: See Table 3
9. Power supply: Voltage 220V±5%, 50±5Hz
|
Model |
Rated Voltage |
Load |
Fuse |
Weight |
|
30/1.1 |
30kV (Peak Value) |
0.1Hz,≤1.1µF |
10A |
Controller:6㎏ booster:20㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |
||||
|
40/1.1 |
40kV (Peak Value) |
0.1Hz,≤1.1µF |
10A |
Controller:6㎏ booster:20㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |
||||
|
50/1.1 |
50kV (Peak Value) |
0.1Hz,≤1.1µF |
15A |
Controller:6㎏ booster:20㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |
||||
|
60/1.1 |
60kV (Peak Value) |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏ booster:45㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |
||||
|
80/1.1 |
80kV (Peak Value) |
0.1Hz,≤1.1µF |
20A |
Controller:4㎏ booster:50㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |
||||
|
90/1.1 |
90kV (Peak Value) |
0.1Hz,≤1.1µF |
20A |
Controller:4㎏ booster:55㎏ |
|
0.05Hz,≤2.2µF |
||||
|
0.02Hz,≤5.5µF |